Greške

Error code Error description
01 Wrong phase – Zamena faze
02 Lack of phase – nema jednu ili dve faze
03 Use side water flow switch
05 High pressure switch-Visok pritisak Cirkulaciona pumpa ne radi
06 Low pressure switch-Nema freona
09 communication error panel - proveri kabel do displeja
11 Time limit
12 Previsoka exhaust temperature A3>B3
15 Water tank water temperature sensor
16 Coil(evaporating) temperature sensor
18 Exhaust temperature sensor
21 Kvar senzora temperatura ambijenta
22 Back water temperature sensor
23 Use side water input temperature sensor
25 Water level switch
26 Use side water input temperature too high
27 Use side water output sensor
29 Gas return sensor
31 Bunarska voda protok prekidač u kvaru
32 Zaštita od smrzavanja. Popravi bunarsku pumpu.
35 Bunarska voda ulazna previše niska
36 Bunar Razlika temperature velika A9-A8>B1
37 Topla strana Razlika temperature velika A6-A5>B2
39 Space heating water output temperature too high
40 Bunarska voda ulazni senzor u kvaru
42 Bunarska voda izlazni senzor u kvaru

PRVO UKLJUČENJE: POSTUPAK

Ako se pojavi Greška 1 u prvom minutu->Zameni faze S i T, ugasi i ponovo ukljući. Kada se ukljući kompresor prati manometar pritiska freona na kutiji toplotne pumpe. Ako predje 25 bara, /na časovniku 1 sat/ u 15 sekundi->ugasi odmah. Proveri vazduh u sistemu ili rad cirkulacione pumpe. Ako objavi grešku 37 -> cirkulaciona pumpa radi ali vazduh .....ozraci. Ako posle par minuta objavi grešku 32, ne uključuj ponovo. Prvo proveri zašto ne prolazi bunarska voda kroz sistem.